Rated voltage (kV) | 40.5 | 72.5 | 126 | 252 | 550 | 800 | |
Rated current (A) | 1600/ 2000 | 3150 | 3150 | 4000 | 5000 | 6300 | |
Rated short circuit breaking current (kA) | 25/31.5 | 40 | 40 | 50 | 63 | 63 | |
Rated short time withstand current/duration (kA/s) | 25/4 31.5/4 | 40/4 | 40/4 | 50/3 | 63/3 | 63/3 | |
Rated peak withstand current (kA) | 63/80 | 100 | 100 | 125 | 160 | 171 | |
Rated power frequency withstand voltage (kV) | To earth | 95 | 350 | 230 | 460 | 740 | 960 |
Between open contacts | 118 | 410 | 230+ 70 | 460+ 145 | 740+ 315 | 960+ 462 | |
Rated lightning impulse withstand voltage (kV) | To earth | 185 | 160 | 550 | 1050 | 1675 | 2100 |
Between open contacts | 215 | 200 | 550+ 100 | 1050+ 200 | 1675+ 450 | 2100+ 650 | |
Rated switching impulse withstand voltage (kV) | To earth | 1300 | 1550 | ||||
Between open contacts | 1175+ 450 | 1425+ 650 | |||||
Mechanical life (times) | 10000 | 10000 | 10000 | 10000 | 10000 |